Many electricity contracts for commercial and industrial sites include a charge based on the highest demand in the billing period, or a contracted capacity that should not be exceeded. The peak is often caused by a short overlap of loads that could have waited a few minutes, such as water heaters, ventilation or EV chargers. Limiting peak demand means detecting that overlap in time and switching some of those loads off for a while. This article explains how demand is measured and how to build staged load shedding with the IF-THEN-ELSE logic on an ICP DAS power meter concentrator, with a worked example.
Instantaneous power changes from second to second. Demand is the average power over a fixed integration period, often 15 minutes; the exact period and the way it is billed are set by the supply contract or the grid operator. Peak demand is the highest of these averages in the billing period. Two consequences matter for control:
Load shedding mainly moves consumption in time. Choose loads that can be interrupted for some minutes without harming the process, product quality or comfort.
The ICP DAS PMC and PMD series power meter concentrators have a built-in IF-THEN-ELSE logic engine for power demand management. Rules are edited on web pages without programming, and the specifications list an unlimited number of rules, timers and schedules, plus internal registers (70 on the PMC-5231). The concentrator reads the power meters and adjusts device operation according to the power status through Modbus I/O modules, which is how load shedding is carried out. Alarms can be sent by email, and on the IIoT models also by LINE or Telegram.
Which values can serve as rule conditions, and how demand is calculated, depends on model and firmware; check the user manual before fixing the design.
These relays switch contactor coils or enable inputs, not the load itself. Wiring them into a distribution board is work for a qualified electrician.
A building has a target maximum demand of 250 kW. All figures here are example values; use your own contract and load data. A PM-3133-RCT500P meter on the main incomer is read by a PMC-5231 over RS-485. An M-7061 relay module on the same RS-485 line drives contactors or enable inputs for three sheddable loads.
| Stage | Load | Power | Max. off-time | Output |
|---|---|---|---|---|
| 1 | Storage water heaters | 36 kW | 30 min | Relay 1 |
| 2 | Ventilation, high-speed stage | 20 kW | 15 min | Relay 2 |
| 3 | EV chargers, enable input | 44 kW | 20 min | Relay 3 |
The rules in plain form (the web configuration looks different):
IF total kW > 225 for 60 s THEN send email "demand warning"IF total kW > 235 for 60 s THEN relay 1 OFFIF total kW > 245 for 60 s THEN relay 2 OFFIF total kW > 250 for 30 s THEN relay 3 OFFIF total kW < 190 for 5 min THEN restore the last relay switched offIF relay n OFF longer than its max. off-time THEN relay n ONThe delays and off-time limits can be implemented with the timer function. The delay stops motor starts and other short spikes, which hardly affect a 15-minute average, from triggering a shed. Test the rules outside working hours with lowered thresholds, and check in the logged data that each stage switches off and restores as intended.
Send technical sales your demand limit, a load profile and a list of loads that can be interrupted, and we will help you plan meters, concentrator and outputs.
The e-USB404 CR adds four independent USB 3.1 Gen 1 host controllers to an AXP-9000-IoT Programmable Automation Controller through a single e-Bus x4 slot. It suits engineers who need several USB devices running at the same time, particularly USB vision cameras that generate large volumes of image data.Each port has its own controller and an LED status indicator, and all four Type-A connectors are accessible on the panel for straightforward wiring. Each port supplies 5 V at up to 900 mA, with overload and short-circuit protection. Power to each port can be switched on and off in software through the SDK, which allows a hung USB device to be reset for failure recovery.Transfer modes: SuperSpeed (5 Gbps), High Speed (480 Mbps), Full Speed (12 Mbps) and Low Speed (1.5 Mbps)Supported on Microsoft Windows 7/8.1/10 and LinuxOperating temperature -25 ~ +60 °CTypical uses are frame grabbing in machine vision inspection, automated optical inspection, quality assurance and medical imaging.ApplicationsMachine vision inspectionAutomated optical inspectionQuality assuranceMedical imaging
The I-7005 CR measures temperature from thermistor sensors and reports readings over RS-485 using the DCON protocol. Its eight input channels can each be configured separately for a different thermistor type, and the module supports a broad list of standard types as well as user-defined types, which are set up by entering Steinhart coefficients where required.Six open-collector digital outputs (sink, NPN) let the module drive alarm signals directly when a monitored temperature needs attention. The thermistor inputs are protected by 3000 VDC intra-module isolation and 120 VDC overvoltage protection, and a built-in dual watchdog supports dependable unattended operation.Key electrical and mechanical details for the I-7005 CR:Power input of +10 ~ +30 VDC with reverse polarity protectionOperating temperature of -25 ~ +75 °CDIN-rail mounting, 72 x 123 x 35 mm (W x L x H)ApplicationsBuilding automationFactory automationMachine automationRemote maintenanceRemote diagnosisTesting equipment
The I-7011 CR is an RS-485 remote I/O module with one differential analog input that accepts voltage, current and thermocouple signals. This blue-cover (CR) ordering code uses the DCON protocol on its serial port, with a configurable baud rate from 1200 to 115200 bps and fixed data format (N, 8, 1).The analog input supports thermocouple types J, K, T, E, R, S, B, N and C, with open thermocouple detection for fault finding. Voltage ranges run from ±15 mV to ±2.5 V, and the 16-bit resolution gives an accuracy of ±0.1% of FSR at a total sampling rate of 10 Hz. Current input (±20 mA) requires an optional external 125 Ω resistor.The digital input can be used as a 50 Hz event counter, and the two open-collector sink outputs can act as high/low alarms, with programmable power-on and safe values. Intra-module isolation is rated at 3000 VDC, and the module is powered from +10 ~ +30 VDC with reverse polarity protection. It mounts on a DIN rail and is rated for operation from -25 ~ +75 °C.ApplicationsBuilding AutomationFactory AutomationMachine AutomationRemote MaintenanceRemote DiagnosisTesting Equipment
The I-7011D CR is a DIN-rail I/O module for measuring voltage, current or thermocouple signals over RS-485 using the DCON protocol. Its single differential analogue input offers 16-bit resolution and supports the standard thermocouple types J, K, T, E, R, S, B, N and C, with open thermocouple detection to flag broken sensor wiring.Beyond the analogue channel, the module provides one dry-contact digital input configured as a 50 Hz event counter and two open-collector digital outputs that can be used for high and low alarm signalling. A 5-digit 7-segment LED display and a power and communication status LED give local visibility without a PC.The module is isolated to 3000 VDC between its internal circuits and offers a built-in dual watchdog for module and communication monitoring. It is supplied from +10 ~ +30 VDC with reverse polarity protection and is rated for operation from -25 ~ +75 °C. This blue-cover ordering code suits building, factory and machine automation, remote maintenance and diagnosis, and test equipment.ApplicationsBuilding AutomationFactory AutomationMachine AutomationRemote MaintenanceRemote DiagnosisTesting Equipment
How PMC and PMD concentrators poll power meters, log to microSD, resend data after network outages and deliver it over Modbus TCP, MQTT, SNMP or FTP.
How to choose single-phase, three-phase or multi-circuit Modbus power meters, size the current transformers and pick Modbus RTU or TCP.
Vi kender ICP DAS-sortimentet og hjælper jer med at finde det rigtige modul, tilbehør eller reservedel.
Kontakt teknisk salg