The WFM-R14 CR adds wireless control to a 14-channel power relay output module. Its Wi-Fi link supports infrastructure and ad-hoc modes, so relay channels can be switched from a monitoring or control network without a run of cable to each output. The module communicates over Modbus TCP and can be integrated into SCADA software.

The 14 outputs comprise 2 x Form A and 12 x Form C contacts. Form A contacts are rated 5 A 250 VAC/30 VDC and 6 A 250 VAC/30 VDC, and the power-on and safe output states can be configured. Wireless security options are WEP, WPA and WPA2, with DHCP support for network addressing and a built-in watchdog for supervision.

The Wi-Fi standard depends on hardware revision: IEEE 802.11 b/g for the non-RevB version and IEEE 802.11 b/g/n for the ReVB version. The manufacturer lists this variant as Asia Only. The package includes an ANT-124-05 antenna, a CA-0910 cable and a 4SNPNA010021G wall-mount kit.

Applications

  • Remote switching of relay outputs in monitoring and control systems
  • Wireless integration of I/O into SCADA software
  • Remote access to relay outputs over Wi-Fi networks
Product type: Wireless I/O Module
Interface: Wi-Fi
Protocol: Modbus TCP
Relay outputs: 14
Power input: +10 ~ +30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail, Wall
Housing: Metal

Specifikationer

Wi-Fi
Transmission Distance (LoS)50 meters (LOS)
StandardIEEE 802.11 b/g (non-RevB version)
IEEE 802.11 b/g/n (ReVB version)
RX Sensitivity-83 dBm @ 11 Mbps (non-RevB version)
-93 dBm @ 11 Mbps (ReVB version)
Output Power8 dBm @ 11 Mbps (non-RevB version)
14 dBm @ 11 Mbps (ReVB version)
ModeInfrastructure & Ad-hoc
EncryptionWEP, WPA and WPA2
Antenna5 dBi (Omni-Directional)
Relay Output
Channels14 (2 x Form A, 12 x Form C)
TypePower Relay
Contact RatingForm A:
5 A 250 VAC/30 VDC
6 A 250 VAC/30 VDC
Operate TimeForm A: 10 ms
Form C: 8 ms
Release TimeForm A: 5 ms
Form C: 4 ms
Electrical Endurance1 x 100000 times 3 A 250 VAC/30 VDC
5 x 10000 times 5 A 250 VAC/30 VDC
1A: 6 x 10000 times
1C: (NO) 3 x 10000 times
1C: (NC) 1 x 10000 times
Mechanical EnduranceForm A: 2 x 1000000 times
Form C: 1 x 1000000 times
Power
Input Range+10 VDC ~ +30 VDC
Consumption2.2 W
Mechanical
CasingMetal
Dimensions (mm)DIN-rail mounting: 33 x 118 x 111 (W x L x H) (Without antenna)
Wall mounting: 73 x 132 x 111 (W x L x H) (Without antenna)
InstallationDIN-rail mounting or wall mounting
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-30 ~ +80 °C
Humidity10 ~ 90% RH, Non-condensing